# Steps on Final Inspection 1. Verify all cables/conduit runs are secured with zip ties or other non- conductive cable clamps to prevent damage from vibration. 2. Ensure all cables that pass-through walls, bulkheads, or any other openings are protected against abrasion by using strain reliefs and/or grommets. 3. Ch…
# WARNING LABELS When an Inverter/Charger is installed in a building the National Electrical Code (NEC) requires a label or plaque to be provided. This label/plaque is required to be easily visible and to inform users of the location of all electrical system disconnects. Buildings with stand-alone power systems (sola…
# HOW TO MOUNT THE INVERTER/CHARGER Before connecting any wires to the Inverter/Charger the unit must be mounted securely in a location which meets the requirements detailed in section 3.2. The GP-IC-2000 weighs: 39 lbs (17.6kg). The GP-IC-3000 weighs: 52lbs (23.6kg). Take the necessary precautions required whilst l…
# FACTORY DEFAULT VALUES The IC Series Inverter/Charger uses default values for the following adjustable settings: ![][1] These settings are only adjustable with the GP-ICR-50 remote, which can be purchased separately from Go Power!. For detailed information on these settings please refer to the remote control man…
**Required Tools ** a. 13mm or adjustable wrench b. Screwdriver (Phillips & Flathead) c. Wire strippers and cutters d. Electric hand drill and drill bits Optional Tools e. Keyhole saw f. Pencil or marker g. Pliers h. Caulking gun i. Sealant j. Digital multimeter k. Torque driver l. Butt splice crimping too…
# 2.1 CAUTIONS/WARNINGS This document contains important safety instructions for the products produced by Go Power! Read all instructions and cautionary markings on the product and on any accessories or additional equipment included in the installation. Failure to follow these instructions could result in severe shoc…
# GFCI (GROUND FAULT CIRCUIT INTERRUPTION) OUTLETS SPECIFICATION Compliance with UL standards requires that Go Power! test and recommend specific GFCIs for use on the AC output of the IC Series. GFCIs shall be installed in the AC output wiring system to proceed all branch circuits. A GFCI is a device that de-energiz…
# Grounding Information If you are installing the IC Series Inverter/Charger on a boat there are some specific guidelines/standards to follow. The Inverter/Charger must be installed adhering to the standards of the ABYC (American Boat and Yacht Council). Some guidelines are outlined below but these notes do not repla…
# DC CABLE CONNECTIONS DIAGRAMS When installing the battery cable ring lug onto the Inverter/Charger DC terminal and the battery post, do not put anything between the ring lug and the metal surface. Incorrectly installed hardware causes a high resistance connection which could lead to poor Inverter/Charger performanc…